M/Y Kaloda chilled-water AC plant: looking for helpKaloda AC: looking for help
M/Y Kaloda, a 32 m Azimut Grande, being lifted by crane from a heavy-lift transport ship on delivery

We need help finding the root cause of our AC plant failure

Are you a marine electrical or refrigeration engineer, a forensic lab, a Climma/Veco or Danfoss MCX technician, or an owner who has seen this before? We would like to hear from you.

I can help find the causeSee the technical facts

The air-conditioning plant on our yacht keeps failing, and no one has yet found out why.

We need an independent engineer or laboratory to find the root cause (the first thing that went wrong), so the new plant does not fail the same way. Photos, test results and the failed parts are kept and available.

We would also welcome advice from people experienced in marine insurance claims where the exact cause of a failure is hard to establish.

I can help find the cause

The story in four steps

  1. What is brokenAll three compressors and parts of the drives have failed. See the measurements and fault codes in plain English.
  2. How it happenedFirst faults in early 2024, 6–7 months after delivery and within warranty; total failure in Aug 2026. Every date in order.
  3. What is still unknownAzimut’s position is that the 2026 failure is unrelated to the 2024 faults. No one has yet established the root cause either way.
  4. How you can helpEngineers, labs and owners with a similar case: tell us what you know.

What happened, in brief

M/Y Kaloda is a 2023 Azimut Grande 32 m. Her chilled-water air-conditioning plant (a central system: three chillers cool a loop of water that is pumped to every cabin; Climma/Veco CWS MODUL 3603 RC, three 120,000 BTU modules) has failed completely. Faults were recorded from early 2024; all three modules were out of service on 29 Jul 2026, one was restored on 3 Aug, and it failed on 19 Aug 2026. All three compressors (the motor-driven pumps at the heart of each chiller) have lost insulation to earth, meaning electricity can leak from the motor windings to the metal body. Damage has also been recorded on the inverter drives (the electronic speed controllers) and line reactors (smoothing coils on the power supply). The root cause has not been determined; an independent investigation is sought. New to the terms? See the glossary, or the full story step by step.

What we are asking for

Failed components are retained under custody. Photographs, fault logs, test records and the commissioning form are available on request: see evidence held and photos.

I can help find the cause

The vessel and plant

Vessel and plant
ItemDetail
VesselM/Y Kaloda, Azimut Grande 32 m, hull 31; delivered June 2023; berthed Pattaya, Thailand
PlantClimma (Veco) CWS MODUL 3603 RC 400/3/50 INV, R410a; 3 modules × 120,000 BTU (360,000 BTU), ‘Gulf’ spec
ControlDanfoss MCX (MCX06D) master; one CAN bus across modules 1–3. Inverter drive per compressor, each fed via a line reactor (Martignoni 40 A, 0.4 mH)
LoopsFresh-water (chilled, glycol) loop to fan coils; seawater condenser loop
SupplyShore power via 65 kVA isolation transformer (always in circuit); Kohler 55EFOZDJ generators (50 Hz)

Who is involved: owner, shipyard, AC manufacturer, insurer, contractors

Diagram of dated referrals between the owner, the builder, the AC manufacturer and its dealer, the insurer (Pantaenius) and contractors, June to October 2026. The same events are listed in the timeline.
Who has been involved and how the issue has moved between parties, 18 Jun to 12 Oct 2026. Text version: timeline. Open full size (pinch to zoom on mobile).

The shipyard built the yacht and installed the AC plant; the manufacturer supplied the chillers through its regional dealer; the insurer (Pantaenius) covers the yacht and appointed a surveyor; local contractors service the plant. The owner is seeking an independent investigation of the root cause.

The case in numbers

Time

Builder (Azimut)116days since the failures were first reported in writing to Azimut (18 Jun 2026). Several technical teams have attended; none has identified the root cause yet.
General54days since compressor 2 failed (19 Aug 2026); the yacht has had no AC cooling since.
Builder (Azimut)22days from the first written report to the first written reply from Azimut after-sales (10 Jul 2026).
AC maker / dealer12–16weeks: replacement plant lead time from order, as stated by the manufacturer's regional dealer (21 Aug 2026).

Messages (18 Jun to 12 Oct 2026)

Insurer (Pantaenius)59AC-related emails with the insurer, including copies; 20 of them were sent by the insurer.
Builder (Azimut)66AC-related emails with Azimut (yard, after-sales and dealer), including copies; 16 of them were sent by Azimut.
AC maker (Veco)24AC-related emails with the AC manufacturer's head office (Veco, Italy), including copies.

Colour key: blue = builder (Azimut), green = AC maker and dealer, amber = insurer (Pantaenius), teal = general. Day counters count calendar days (Bangkok date) and update automatically; the figures shown without scripts are as of 12 Oct 2026. Email counts are as of 12 Oct 2026: AC-related messages in the owner's mailbox sent to, received from or copied to each party, excluding automatic replies, recalls, duplicate re-sends and unrelated policy administration. If you believe a count is wrong, tell us and we will correct it.

See the timeline, technical facts, photos and the background and case files.

Frequently asked questions

What happened to the AC on M/Y Kaloda?

The Climma/Veco CWS MODUL 3603 chilled-water plant (three 120,000 BTU modules) has failed completely. Faults were recorded from early 2024. All three modules were out of service on 29 Jul 2026; unit 2 was restored on 3 Aug and its compressor failed on 19 Aug 2026. All three compressors lost insulation to earth, and inverter and line-reactor damage was recorded.

Is the root cause known?

No. The root cause has not been determined; an independent investigation is sought.

How can I help?

If you are a marine electrical or refrigeration engineer, a forensic laboratory, a technician who knows Climma/Veco or Danfoss MCX equipment, or an owner with a similar experience, please use the I can help page.

What is this site for?

It is a factual record published for information, to help find the cause and to share general lessons with other owners. Corrections are welcome.