Azimut Grande 32M: chilled-water AC failure, root cause wantedAzimut Grande 32M: AC root cause wanted

Climma CWS MODUL chiller alarm codes: what we recorded

Root cause not determined; independent investigation sought. This page explains, in plain English, the alarm families shown by the Danfoss MCX controller on a three-module Climma/Veco CWS MODUL 3603 chilled-water plant, and lists every alarm recorded on this yacht. Meanings follow the manufacturer’s alarm-code sheet (C859-05) and the published CWS MODUL manual section headings. It is not a service manual; always follow the manufacturer’s instructions.

Alarm families on a CWS MODUL plant
CodesFamilyWhat it generally meansRecorded here
22, 23, 24CAN-BUS MOD 1/2/3 KOThe master controller has lost data contact with module 1, 2 or 3 over the CAN bus. Causes can include cabling, connectors, termination or a module that has stopped responding.Yes: modules 1, 2 and 3, 2024 and 2026
7, 45, 52, 55Flow alarmsToo little water flow detected (chilled-water or seawater side). Causes can include a blocked strainer, air, a pump fault or a faulty flow sensor.Yes: unit 2, 2024 and Jul 2026
30DRIVE ALARMA generic alarm from the inverter drive that powers the compressor. The specific cause (for example overheating, over-current or under-voltage) is a sub-code, shown when the alarm line is highlighted on the controller and Enter is pressed.Yes: units 1, 2 and 3; sub-codes partly recorded
16, 53AntifreezeChilled-water temperature too low.Not recorded
50Low pressure (LP)Refrigerant low-pressure switch tripped; manual reset.Not recorded
1, 2, 46–48Probe faultsA temperature sensor reads out of range or is disconnected.Not recorded

How to read a Code 30 drive alarm

  1. Photograph the alarm list before resetting anything.
  2. Highlight the Code 30 line on the controller and press Enter to see the drive’s own sub-code.
  3. Photograph that screen too, and note the date and time shown and whether the yacht was on shore power or generators.
  4. Check the controller clock against real time, so the event log can be lined up with other records.

Every alarm recorded on this yacht

Dates are indicative because the controller clock setting has not been verified, and Code 30 sub-code decodes have not been confirmed by the manufacturer.

MCX fault-code record
#DateUnitCodeScreen textMeaning (C859-05)In plain English
102-01-24 07:51330DRIVE ALARMInverter alarm, sub-code 3: inverter overheatingThe drive for compressor 3 got too hot and shut down
202-01-24 08:18330DRIVE ALARMInverter overheatingSame again, 27 minutes later
302-01-24 09:01230DRIVE ALARMInverter overheatingThe drive for compressor 2 got too hot
402-01-24 10:14130DRIVE ALARMInverter overheatingThe drive for compressor 1 got too hot: all three drives overheated within about 2.5 hours
503-03-2427→52Low fresh water flow / repeated flow alarmLow FW flow, then 4th repeated flow alarmWater stopped flowing properly through module 2, repeatedly
6Aug-24plant—Whole-plant shutdownReported as CAN communication fault; code not recordedThe whole plant stopped; reported as the controller losing contact with the modules
713-12-251, 2—DIS-VOLT state, ~30 s after start, no alarm loggedNot a code; matches Code 30 sub-code 10 “temporary undervoltage ×3 – DISUV”Drives saw a brief low-voltage dip three times just after start; no alarm was saved
8May-26plant—Shutdowns incl. display, no alarm loggedNo codeThe plant, including its display, switched off with no alarm saved
927-07-26 00:49122CAN-BUS MOD 1 KOMissing CAN communication, module 1The controller lost contact with module 1
1027-07-26 02:24252FLOW METER ALARMRepeated FW flow alarm (4th)Module 2 water-flow alarm, fourth repeat
1127-07-26 02:34252FLOW METER ALARMRepeated FW flow alarmModule 2 water-flow alarm again
1229-07-26 11:3427FLOW METER ALARM (autoreset)Low FW flow; flow 6.71→0.00 m³/h, plate 62.3 °CModule 2 water flow dropped to zero and its drive plate reached 62.3 °C
1311-08-26 17:08223CAN-BUS MOD 2 KOMissing CAN communication, module 2The controller lost contact with module 2
1411-08-26 20:33223CAN-BUS MOD 2 KOMissing CAN, module 2Lost contact with module 2 again
1511-08-26 20:34230DRIVE ALARMInverter alarm, sub-code 1: inverter over-currentThe module 2 drive saw too much current
1611-08-26 20:57230DRIVE ALARMInverter over-currentToo much current again on module 2
1719-08-26 12:54223CAN-BUS MOD 2 KOMissing CAN, module 2Lost contact with module 2
1819-08-26223→30—Missing CAN mod 2, then inverter over-current; ~5.6 Ω phase to earth measuredLost contact, then too much current; compressor 2 then measured as shorted to earth (about 5.6 Ω)
19undated3 / 2 / 124 / 23 / 22Active alarm listMissing CAN, modules 3, 2 and 1 – all three off the busNone of the three modules was talking to the controller
20undatedmaster—MASTER ALARM, water 30.7 °C, FWP OFF, COMP 0/3, WATER FLOW SHUT DOWNPlant shut down on FW flow, no compressorsThe whole plant stopped because water was not flowing; no compressors running

Have you seen the same sequence (CAN dropouts, flow alarms and Code 30 drive alarms) on a Climma CWS plant? Please tell us. See also the technical facts and the timeline.